· Connection

Remove the cover of the solar inverter

before connecting an interface cable. Pay

heed to all safety hints (Pages 90 and 91).

You will find the necessary cable terminal

block with the RS 485+, RS 485-, GND_G,

TX, RX, GND_G, TX 2, RX 2 connections on

the board in the centre, bottom left

(see figure on the left). Note the following

terminal configuration:

RS 232: GND, RX, TX

RS 485: RS 485+, RS 485-

(The remaining signals, TX2 and RX2, are

only for service purposes.)

Use a small screwdriver. Press the orange

terminal. The terminal will open.

Insert the cable stripped to a minimum of

11 mm into the respective terminal hole.

Release the screwdriver. The cable is fixed

in the connection.

Once again, check that the cable connec-

tion is firmly located.

Seal the unrequired cable glands by

placing a spare piece of cable in the gland

hole and tightening with the screw clamp.

Please heed the description on the

Sunways NT Monitor software in

Chapter 3.2.