· The DC voltage can be up to 750 V. The

unit may only be opened by a qualified

electrician!

· Always disconnect the PV generator side

first by opening the PV generator switch,

and then the grid connection by isolating

the relevant mains fuse!

· If you do not have a PV generator switch

in your PV system, you must disconnect

the grid connection first of all by isola-

ting the relevant mains fuse. However, a

«grid error» will be entered in the error

memory of the solar inverter!

· Disconnection of the PV generator by

removing the TYCO SOLARLOK DC con-

nectors must never be performed under

load. In the event of non-compliance, the

connectors could be damaged by a strong

electric arc. In this case, the relevant con-

nectors must be replaced!