Changing the Spectra 12000 Library Air Filters

Spectra 12000 libraries have three replaceable filters inside the front
door. Inspect filters every three to four months and replace as necessary.
If a filter is contaminated, replace it with a new filter. A clogged air filter
blocks air movement within the library, resulting in higher temperatures
inside the library. High temperatures may cause operational errors. (See
Purchasing Additional Accessories on page 153.)

To check and replace the filter:

1.

Open the front door of the library. To do this:

2.

Go to the Library Controller. Select Status from the General toolbar.
The General Status screen appears (Figure 11-1).

3.

Select Robotics. The System Setup screen appears. At the bottom of
this screen, tap the button marked Open System Door. This disengages
the solenoids (electronic door latches).

4.

Use the door key to unlock the front door of the library.

5.

You can now open the door.

6.

Unscrew the two screws that attach the filter assembly to the back of
the door.