Protection functions & controls, 1 five seconds stand-by (fan), 2 two minutes stand-by (comp.) – LG General Wall Mounted-Inverter Type User Manual

Page 16: 3 hot start

Advertising
background image

16 Room Air Conditioner

Part 2 Functions & Controls

5.1 Five Seconds Stand-by (fan)

• The indoor unit fan rotates after 5 seconds when unit is turned on.

5.2 Two Minutes Stand-by (comp.)

• Compressor starts two minutes later, after it is turned off

5.3 Hot start

• When unit starts in the heating mode to prevent cold wind blowing, the indoor fan does not rotate until the temp. of

heat exchanger reaches 30°C(86°F)(model by model)

5.4 Freeze prevention (Protection of the evaporator pipe from frosting)

• If the indoor pipe temperaure is below 0°C(32°F) in 7 min. after the compressor operates without pause while in cool-

ing cycle operation mode,

➔ compressor, outdoor fan are turned off.

• When indoor pipe temp. is 7°C(44.6°F) or higher after 2 min pause of compressor

➔ compressor, outdoor fan is turned

on according to the condition of the room temperature.

5. Protection Functions & Controls

Comp. free

Comp. Step 4
Comp. Step 2

Comp. off

T1

3˚C(37.4˚F)

6˚C(42.8˚F)

7˚C(44.6˚F)

Indoor pipe
temp.

T1: 0 ~ 2°C(32~35.6°F)

NOTE: Some Models are different by T1.