22 Room Air Conditioner

Part 2 Functions & Controls

5.8.2 18,24,30kBtu/h Model

• Function

: Power module failure protection by checking the temperature of heat sink.

There is a temperature sensor for checking the heat sink temperature.

• Heat sink sensor failure error

Short Check : if temperature

≥130°C(266°F)

Open Check : if temperature < - 30°C(-22°F)

System will go in self diagnosis (Error code 65) is displayed and product stops.

• Heat sink temperature control

a) Heat sink temperature < T2

: No limitation on compressor frequency

b) T2

≤ heat sink temperature < Toff : Compressor frequency down by 5 Hz

c) Heat sink temperature

≥ Toff

: Compressor will be off.

System will stop if this situation occurs 5 times in 1 hour and error code will be generated also self diagnosis will
start.

If high temperature situation occurs 5 times in 1 hr system counts 1 error and after that 4 times if this situation
occurs system stops and give error code.

If the temperature reached Toff condition system will count 5 times after that and system will stop with error
code.

COMP

Hz

Toff=85

°C(185°F)

T2=75

°C(167°F)

OFF

Set

frequency

Set

frequency

Set

frequency

Heat Sink temp

5 Hz

Down

5 Hz

Down

T1=70

°C(158°F)