46 Room Air Conditioner

Part 4 Trouble Shooting

7. Self-diagnosis Function

Error Indicator

• The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
• Error mark is ON/OFF for the operation LED of evaporator body in the same manner as the following table.
• If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.

9, 12kBtu/h Model

1 time

1time

3 sec

2 times

2 times

3 sec

4 times

4 times

3 sec

5times

5times

3 sec

6times

6times

3 sec

7times

7times

3 sec

3 sec

3 sec

2 times

3 sec

2 times

3 sec

1time

3 sec

1time

3 sec

1time

3 sec

1

2

4

5

6

7

Error Indicator

Error

Code

Cause of Error

Display

Indoor Outdoor

Indoor

Operation

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

• Indoor Temp. sensor error
- Sensor open or short

• Heat Sink sensor error
- Sensor open or short
- Heat Sink temp is over 95

°…

• Communication error

• Outdoor Temp. sensor error
- Sensor open or short

• DC Peak error

• Over current error (CT2)

ON

ON

ON

OFF

SHUT

DOWN

SHUT

DOWN

9times

9times

3 sec

10 times 10 times

3 sec

10

ON

• Outdoor fan lock error

• D-Pipe TH. is short or open.

(BLDC fan model only)

OFF

8times

8times

3 sec

8

• Indoor fan lock error
(BLDC fan model only)

OFF

9