58 Room Air Conditioner

Part 4 Trouble Shooting

3) Troubleshooting CH21

Comp

Copper
pipe

Resistance(

Ω) at 20°C(68°F)

Resistance(

Ω) at 20°C(68°F)

0.64

0.64

0.64

Inverter

comp.

V-W

W-U

U-V

Terminal

0.8

0.8

0.8

Constant

comp.

2M

2M

2M

Inverter

comp.

V-GND

W-GND

U-GND

Terminal

2M

2M

2M

Constant

comp.

V

U

W

Comp

21

DC Peak

• Instant over current
• Over Rated current
• Poor insulation of IPM

• An instant over current in the U,V,W phase

- Comp lock
- The abnormal connection of U,V,W

• Over load condition

- Overcharging of refrigerant
- Pipe length.

• Poor insulation of compressor

Error

code

Title

Cause of error

Check point & Normal condition

Check Point

1. Check the wire connection. (U,V,W)

2. Check the load condition. (Refrigerant, Pipe length, …)

→ Adjust the load condition

3. Check the electricity leakage of the compressor.

→ Normal : Over 2MΩ.

4. Check the resistance of compressor.

→ Normal : 0.65Ω(INV), 0.8Ω(Cons.) → No difference at each terminal.

5. Check the insulation from water at IPM part.

→ Check the trace of water.

6. Check the IPM circuit.