Cycle troubleshooting guide, Notice – LG General Wall Mounted-Inverter Type User Manual

Page 39

Advertising
background image

Service Manual 39

Part 4 Trouble Shooting

Trouble analysis

1. Check temperature difference between intake and discharge air, and operating current.

All amount of refrigerant leaked out.
Check refrigeration cycle.

Refrigerant leakage
Clog of refrigeration cycle
Defective compressor

Excessive amount of refrigerant

Normal

Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relatively higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.

NOTICE

Temp. difference

: approx. 0°C(1°F)

Current

: less than 80% of

rated current

Temp. difference

: approx. 8°C(16°F)

Current

: less than 80% of

rated current

Temp. difference

: less than 8°C(16°F)

Current

: near the rated

current

Temp. difference

: over 8°C(16°F)

Temp. Difference

Operating Current

5. Cycle Troubleshooting Guide