Test run flow chart – LG General Wall Mounted-Inverter Type User Manual

Page 32

Advertising
background image

32 Room Air Conditioner

Is cold air discharged for

more than 3 minutes ?

START

Test operation for indoor unit

Operation mode change

to Heating mode

Operate the unit in cooling mode.

Does Test operation start?

Refer to part4, 7 Electric part

Yes

No

Yes

Refer to part4, 5 Cycle part

No

Is hot air discharged ?

After Hot Start

NOTE: When outdoor temperature is low,the unit is operated to Heating mode

Yes

No

Is there any temperature

difference between intake and

discharged air?

Yes

No

Is the operating current

normal ?

Yes

Normal

Refer to Troubleshooting

Guide

No

* Check the load (In/Out Temp.)
* Check pipe length and amount of

refrigerant

* Check for abnormal sound in

outdoor unit (comp.,Fan, others )

Part 3 Test Run

2. Test Run Flow chart