Test run flow chart – LG General Wall Mounted-Inverter Type User Manual
Page 32
Advertising
32 Room Air Conditioner
Is cold air discharged for
more than 3 minutes ?
START
Test operation for indoor unit
Operation mode change
to Heating mode
Operate the unit in cooling mode.
Does Test operation start?
Refer to part4, 7 Electric part
Yes
No
Yes
Refer to part4, 5 Cycle part
No
Is hot air discharged ?
After Hot Start
NOTE: When outdoor temperature is low,the unit is operated to Heating mode
Yes
No
Is there any temperature
difference between intake and
discharged air?
Yes
No
Is the operating current
normal ?
Yes
Normal
Refer to Troubleshooting
Guide
No
* Check the load (In/Out Temp.)
* Check pipe length and amount of
refrigerant
* Check for abnormal sound in
outdoor unit (comp.,Fan, others )
Part 3 Test Run
2. Test Run Flow chart