5.10 DC Peak control

5.10.1 DC Peak Current Error by a fault signal of IPM

• If the operating current of IPM reaches 35A

3A, the compressor stops instantly.

• If DC PEAK occurs 5 times within 1 hour, the appliance turns off and displays Error Code 6(9,12kBtu/h Model) / Error

Code 21(18,24,30kBtu/h Model).

5.10.2 DC Peak Current Error by the compressor lock

• If the DC LINK voltage below DC 140V occurs 5 times within 1 hour while the compressor is operating, the appliance

turns off and display Error Code 6(9k,12k Model) / Error Code 23(18k,24k,30k Model).

5.10.3 DC Peak Current Error by the Outdoor Fan Lock

• If this problem occurs 5 times within 1 hour in case of the temperature of outdoor pipe TH is over 65°C(149°F) while

the compressor is operating, the appliance turns off and displays Error Code 6(9,12kBtu/h Model) / Error Code
61(18,24,30kBtu/h Model).

5.11 Discharge Pipe Temp Control

5.11.1 9,12kBtu/h Model

• If the temperature of the discharge pipe of compressor reaches over 130°C(266°F) or below -30°C(-22°F) the com-

pressor stops instantly.

• The compressor operating frequency is limited according to the compressor dome TH. (Refer to below Fig.)

• Temperature range of COMP SPEC varies by 10°C(50°F).

T off : 110°C(230°F) ( Model by model )

T2 : 100°C(212°F) ( Model by model )

D-Pipe Temp.

COMP Freq.

Free

Free

Fh min

OFF

Fc-1

Fc-1

Fc-2

Fc-2

∆T = (T off - T2)/2
T1 = T2 - 2 * ∆T

T3 = T2 +

∆T

T off

°C

T2

°C

T3

°C

T1

°C

-13

°C(8.6°CF)

NOTE: Some Models are different by T1, and T2.