Check point – LG General Wall Mounted-Inverter Type User Manual

Page 64

Advertising
background image

64 Room Air Conditioner

Part 4 Trouble Shooting

9) Troubleshooting CH41, CH44, CH45, CH46, CH47, CH65

41

44

45

46

47

65

D-pipe sensor (Inverter)

Air sensor

Condenser Pipe sensor

Suction Pipe sensor

D-pipe sensor (Constant)

Heat sink sensor

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

• Open / Short
• Soldered poorly
• Internal circuit error

• Normal resistor : 200k

Ω / at 25°C(77°F) (Unplugged)

• Normal voltage : 4.5VDC / at 25°C(77°F) (plugged)

• Normal resistor : 10k

Ω / at 25°C(77°F) (Unplugged)

• Normal voltage : 2.5VDC / at 25°C(77°F) (plugged)

• Normal resistor : 5k

Ω / at 25°C(77°F) (Unplugged)

• Normal voltage : 2.5VDC / at 25°C(77°F) (plugged)

• Normal resistor : 5k

Ω / at 25°C(77°F) (Unplugged)

• Normal voltage : 2.5VDC / at 25°C(77°F) (plugged)

• Normal resistor : 200k

Ω / at 25°C(77°F) (Unplugged)

• Normal voltage : 4.5VDC / at 25°C(77°F) (plugged)

• Normal resistor : 10k

Ω / at 25°C(77°F) (Unplugged)

• Normal voltage : 2.5VDC / at 25°C(77°F) (plugged)

Display

code

Title

Cause of error

Check point & Normal condition

Check Point

1. Estimate the resistance of each sensor.(Unplugged)

2. Estimate the voltage of each sensor.(Plugged)

3. If the resistance of the sensor is 0 k

Ω or ∞, then sensor is abnormal.

If the voltage of the sensor is 0 V or 5VDC, then sensor is abnormal.