52 Room Air Conditioner

Part 4 Trouble Shooting

Cause of error

6

• Supplied power is not normal
• Comp Connector (CN-U,V,W) is disconnected or inserted to wrong
position
• Compressor is damaged (coil short)

➔ replace compressor

• Too much Refrigerant
• Defect in outdoor pcb assembly

➔ replace pcb assembly

DC Peak Error

Supplied voltage to
Outdoor pcb is about
AC 208~230V ?

Is connector (CN-U,V,W)
connected to compressor and
inserted to pcb in right position ?

YES

No

Check power source

No

Check CN-U,V,W connector
(U : RD, V : BL, W : YL)

Check flow

Refrigerant pressure is right ?

YES

No

Check refrigerant pressure
and adjust.

Is the compressor right ?

YES

No

Check resistance

Between U-V, V-W, U-W port.

→ Short / Open circuit

(Comp.motor coil error)

→ normal : 1 ~2Ω

Between U,V,W and Body

→ normal : over 10MΩ

Inverter components in outdoor pcb assembly are
right ?

YES

No

* 9 K/12K Model
Check

Short of SPM3 pins (GND - P, U, V, W pin)
Direction of D01Z~D03Z, C08Z,10Z,12Z,16Z
Assembling state of R01P ~ R21P & IC01P
Assembling state of screw between INV-IC &

Heat-sink

DC 15V output of Power module.

V

U

W

Description

Cause of error

Error code