Trouble 2 – LG General Wall Mounted-Inverter Type User Manual

Page 42

Advertising
background image

42 Room Air Conditioner

Part 4 Trouble Shooting

Turn on main power.

While the compressor has been stopped, the compressor does not operate

owing to the delaying function for 2 minutes after stopped.

When the compressor stopped Indoor Fan is driven by a low speed.

At this point the wind speed is not controlled by the remote controller.

(When operated in the Sleeping Mode, the wind speed is set to the low speed as force).)

Caused by the remote controller.

Caused by other parts except

the remote controller

When the mark ( ) is displayed in LCD

screen, replace battery.

Check the contact of CN-DISP 1, 2 connector

Check DISP P.C.B Ass'y

-Voltage between CN-DISP1

-

: DC +5V

Check point
• Check the connecting circuit between

MICOM PIN

and CN-DISP1 PIN

• Check receiver ass'y

Product doesn't operate with the remote controller. (9~30kBtu/h Model)

Trouble 2