54 Room Air Conditioner

Part 4 Trouble Shooting

8

• Indoor fan is locked or separated
• Fan connector is not connected to indoor pcb assembly
• Defective in DC-fan driving circuit

Indoor fan is locked

(BLDC fan model only)

Indoor fan is rotating ? (1)

Indoor fan is rotating ? (2)

YES

No

Check indoor unit
- remove obstacles in
indoor unit
- fan assembled correctly.

No

Check soldering state of
CN-Motor1 & assembling
state of DC Fan connector

Check flow

DC–fan driving circuit is right ?

YES

No

Check DC Fan Driving circuit
(Soldering state & Direction)
- R01F~R09F, C01F~C03F,
IC01F~IC03F, Q01F~Q02F, ZD01F

9

• Outdoor fan is locked by an obstacle (ex : branch of tree, bar…etc)
• Fan connector is not connected to outdoor pcb assembly
• Defective in DC-fan driving circuit

Outdoor fan is locked

(BLDC fan model only)

Outdoor fan is rotating ? (1)

Outdoor fan is rotating ? (2)

YES

No

Check outdoor unit
- remove obstacles in
outdoor unit

No

Check connector is not
connected to outdoor pcb
assembly (CN-FAN2)

Check flow

DC–fan driving circuit is right ?

YES

No

Check DC Fan driving circuit
(Soldering state & Direction)
- R01F~R05F, C01F~C03F,
Q01F~Q04F, ZD01F

Description

Cause of error

Error code

Description

Cause of error

Error code