26 Room Air Conditioner

Part 2 Functions & Controls

5.11.2 Inverter Compressor (18,24,30kBtu/h Model)

1) There can be two situations

(a) Sensor is failed (Error Code 41)

(b) Abnormal high temperature discharge temperature (error code for high discharge will be generated)

Both cases unit will stop.

2) Compressor working

(a) If discharge pipe temperature T1 No limitation on compressor frequency

(b) T2

≤ discharge pipe temperature T off (Hysteresis control) Compressor frequency down by 5Hz and expan-

sion valve up by 10 pulse in every 1 min.

(c) Discharge pipe temperature

≥ Toff Compressor will be off

System will stop if this situation occurs 5 times in 1 hour and error code will be generated.

Expansion

valve

10

Pulse Up

10

Pulse Up

COMP

Hz

Toff(105)

°C(221°F)

T1(90)

°C(194)°F

T2(95)

°C(203)°F

5 Hz

Down

5 Hz

Down

OFF

Set

Set

D-Pipe temp

Stop control

Set

Set

Set