Troubleshooting guide(9,12kbtu/h model) – LG General Wall Mounted-Inverter Type User Manual

Page 49

Advertising
background image

Service Manual 49

Troubleshooting Guide(9,12kBtu/h Model)

Part 4 Trouble Shooting

Description

Cause of error

1

• Indoor TH. (sensor) is short or open
• Indoor TH. (sensor) is not connected to the indoor pcb assembly
• Damage or defect on the sensing circuit of indoor pcb assembly.
(R01H, R02H, R03H, R04H, C01H, C02H)

Indoor TH. is short or

open

Indoor TH. is connected to
Indoor pcb assembly ?

Indoor TH. is right ?

YES

No

- Connect to CN-TH1 in
indoor pcb assembly

Sensing circuit of indoor
pcb is right ?

No

Check Indoor TH.
- Measure resistance of TH.
(air : about 10k

Ω at 25°C(77°F),

pipe : about 5k

Ω at 25°C(77°F)

YES

No

- Check soldering state of
R01H ~ R04H, C01H, C02H

Check flow

2

• Outdoor TH. (sensor) is short or open
• Outdoor TH. (sensor) is not connected to the outdoor pcb assembly
• Damage or defect on the sensing circuit of outdoor pcb assembly.
(R03H~R06H, C02H, C03H)

Outdoor TH. is short or

open

Description

Error code

Error code

Cause of error

Outdoor TH. is connected to
outdoor pcb assembly ?

Outdoor TH. is right ?

YES

No

- Connect to CN-TH1 in
outdoor pcb assembly

Sensing circuit of outdoor
pcb is right ?

No

Check outdoor TH.
- Measure resistance of TH.

YES

No

- Check soldering state of
R03H ~ R06H, C02H, C03H

Check flow

(air : about 10k

Ω at 25°C(77°F),

pipe : about 5k

Ω at 25°C(77°F)