40 Room Air Conditioner

Part 4 Trouble Shooting

2. Check temperature and pressure of refrigeration cycle.

1. The suction pressure is usually 8.5~9.5 kg/cm

2

.g at normal condition.

2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with

putty.

NOTICE

Suction pressure

Temperature

(Compared with

(Compared with

Cause of Trouble

Description

the normal value)

the normal value)

High

Defective compressor

Current is low.

Normal

Excessive amount of

High pressure does not quickly

refrigerant

rise at the beginning of operation.

Insufficient amount of

Current is low.

Lower

Higher

refrigerant(Leakage)
Clogging

Higher