Maintenance

105

If you have a different model battery, contact Liebert Global Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once

disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.

The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.

When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and

insulate the cables connected to the battery. Secure each battery shelf with retaining screws when

maintenance is complete.

Rack-Mounted Batteries

If the UPS system uses a battery other than a factory-supplied Matching Battery Cabinet, perform

maintenance on the battery as recommended in the battery manufacturer’s maintenance manual,

available on the manufacturer’s Web site.

Table 13

Battery retorque values

Battery

Manufacturer

Battery

Model No.

Retorque

Value

Dynasty

UPS12

-

270(FR)

32 lb

-

in.

UPS12

-

310(FR)

52 lb

-

in.

UPS12

-

370(FR)

52 lb

-

in.

UPS12

-

475(FR)

100 lb

-

in.

C&D Batteries

LS12

-

100 100

lb

-

in.

12G

-

17

100 lb

-

in.

Enersys

HX205

60 lb

-

in.

HX300

60 lb

-

in.

HX370

60 lb

-

in.

HX400

60 lb

-

in.

HX500

60 lb

-

in.

Table 14

Battery voltage record

Date

Float Voltage (Volts DC)

Nominal Voltage (Volts DC)

Ambient Temp. (°F)

(To be completed by Liebert Global Services customer engineer at time of start-up)

Advertising