Figure 27 battery cycle monitoring summary screen, Operation 43 – Liebert 1000kVA User Manual

Page 49

Advertising
background image

Operation

43

The Summary screen (Figure 27) shows Total Number of Discharge Cycles, Accumulated Battery

Time, Accumulated Battery Amp Hours, Accumulated Battery Kilowatt Hours and Battery Tempera-

ture. During a battery discharge event, the screen changes to show information about the present dis-

charge cycle. The screen displays Active Cycle Time in place of Accumulated Battery Time and shows

Active Battery AH and Active Battery kWH instead of accumulated values.

Figure 27 Battery cycle monitoring summary screen

Figure 28 shows a typical detail screen for the 91-240 Seconds Discharge category. This information

can be collected remotely, through the optional communications board and modem, by a remote termi-

nal or a personal computer equipped with a modem and communications program. See 3.2.15 - Com-

munication Interfaces for more information.

Figure 28 Typical data on discharge cycles of 91 to 240 seconds duration during the recording period

NOTE
This information is applicable to systems with separate batteries for each module. If the

modules share a common battery, select one module to do the monitoring and disregard

the other(s).

7
15 min. 32 sec.
71
34
25°C / 77°F

Total No. of Cycles . . . . . . . . . . . . .
Accumulated Battery Time . . . . . . .
Accumulated Battery AH . . . . . . . .
Accumulated Battery KWH . . . . . . .
Battery Temperature . . . . . . . . . . . .

Battery Cycle Monitoring Summary

EXIT

SELECT :

© 1989-2003

EXIT

Event

Date

Time Duration Min. Volt Max. Amp Start KW Start Temp

15

4/12/95

10:31

235

477

110

70

68

12

3/25/95

20:21

98

479

97

37

65

9

3/13/95

7:35

139

467

173

69

67

5

2/07/95

17:22

199

478

95

40

70

2

11/24/94

12:33

95

477

83

39

69

Total 91-240 se c. Cycl 5

CURSOR UP

CURSOR DOWN

CHOOSE

UP :

DOWN :

SELECT :

© 1989-2003