5 electrical specifications, Electrical specifications – Liebert 1000kVA User Manual

Page 117

Advertising
background image

Specifications

111

5.5

Electrical Specifications

RECTIFIER INPUT

Input Voltage

Standard voltages for 100 - 450kVA units: 208, 480 and 600VAC

Standard voltages for 500 - 1000kVA units: 480 and 600VAC

Other voltages available on request. 3-phase, 3-wire plus ground.

Voltage Range

+10%,

-

15% (no battery discharge at

-

20%)

Frequency Range

57 Hz to 63 Hz

Subcycle Magnetization Inrush

Less than 3 times normal full load input current for UPS models without optional

input isolation transformer. Less than 8 times normal full load input current for

models with optional input isolation transformer and optional input filter

Input Current Walk-In

From 20% to 100% in 15-20 seconds

Current Limit

Maximum of 125% normal full load input current

Current Distortion

Less than 30% reflected THD typical at normal full load input current. Less than 7%

reflected THD typical at normal full load input current with optional input filter

500kVA to 750kVA models with optional 12-pulse rectifier: Less than 9% reflected

THD typical at normal full load input current. Less than 4% reflected THD typical at

normal full load input current with optional input filter

Power Factor

0.85 minimum lagging at full load

0.92 minimum lagging at full load with optional input filter

BYPASS INPUT

Input Voltage

Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. 3-phase, 4-wire

plus ground or 3-phase, 3-wire plus ground. Other optional voltages available.
Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3-phase, 3-wire plus ground

(ungrounded or corner grounded delta). Other optional voltages available.

Voltage Range

±5% for manually initiated bypass transfer

±10% for automatically initiated uninterrupted transfer

Frequency Range

59.5 Hz to 60.5 Hz

Voltage Transient

±4% for manually initiated bypass transfer

CRITICAL LOAD OUTPUT

Output Voltage

Standard voltages - 208/120 VAC, 480/277 VAC, 600/346 VAC. Other optional

voltages available.

SCC output: 3

-

phase, 3

-

wire plus ground or 3

-

phase, 4

-

wire plus ground

Module output to SCC: 3

-

phase, 4

-

wire plus ground (neutral required)

Optional voltages - 208 VAC, 480 VAC, 600 VAC. 3

-

phase, 3

-

wire plus ground

(ungrounded or corner grounded delta). Other optional voltages available.

Voltage Regulation

±0.5% for balanced load

±2% for unbalanced load

Voltage Adjustment Range

±5% manually

Line Drop Compensation Range

Up to +5% automatic load dependent

Frequency

595 Hz to 605 Hz

Slew Rate

0.01 to 1 Hz per second, adjustable

Phase Balancing

120° ±1° for balanced loads

120° ±3° for 50% unbalanced loads

Voltage Imbalance

20% Unbalanced Load

50% Unbalanced Load

±1% from the arithmetic average of the 3 phases

±2% from the arithmetic average of the 3 phases

Voltage Transient

20% Load Step

50% Load Step

100% Load Step

Loss or Return of AC Input Power

Manual Transfer of 100% Load

±4% RMS

±4% RMS for 100-750kVA units; ±5% RMS for 1000kVA units

±5% RMS for 100-750kVA units; ±8% RMS for 1000kVA units

±1% RMS

±4% RMS

Voltage Transient Recovery Time

To within 1% of steady state output voltage within 50 milliseconds

Voltage Harmonic Content

Maximum 5% RMS total, for any combination of linear and nonlinear loads

Maximum 3% RMS single, for linear loads

Module Overload Capacity

at Full Output Voltage

(System overload capacity depends on

the configuration of on-line modules.)

104% of full load rating continuously

125% of full load rating for 10 minutes

150% of full load rating for 30 seconds

(with ±2% voltage regulation)

Fault Clearing

Up to 300% of normal full load current subcycle; up to 500% of normal full load

current for up to 40 milliseconds with bypass available; up to 1000% of normal full

load current for up to 16 milliseconds with bypass available

Advertising