Table 10 alarm messages - summary, Table 10, Alarm messages - summary – Liebert 1000kVA User Manual

Page 75

Advertising
background image

Operation

69

Table 10

Alarm messages - summary

Alarm Message

MMU

SCC

Special Functions

Input Fail

X

DC Ground Fault

X

D, L, S

DC Capacitor Fuse Blown

X

D, F, S

Battery CB Open

X, R

D, S

Battery Discharging

X, R

R

D, S

Low Battery Warning

X, R

R

D, S

Low Battery Shutdown

X

D, F, L, S

DC Overvoltage Shutdown

X

D, F, L, S

Load On Bypass

X, R

D

Auto Transfer to Bypass

E

D, F

Auto Retransfer Primed

X

Manual Reset/Retransfer

X

Static Switch Unable

X

D, S

Bypass Not Available

X

D, L, S

Bypass Phase Sequence Wrong

X

Input Current Unbalanced

E

D

Control Power Fail

X, R

X

D, L, S

Output Over/Under Frequency

X

D, L, S

Output Undervoltage

X

D, F, L, S

Output Overvoltage

X

D, F, L, S

Overload

X

X, R

D, S

Overload Transfer

X

D, F, L, S

Inverter Non-Synchronized

X

Module N (1-6) Off Line

R

X

D

Overload Shutdown

X

D, F, L, S

Reverse Power

X

D, F, L, S

Rectifier Fuse Blown

X

D, F, S

Inverter Fault

X

D, F, S

Hardware Shutdown

X

D#

Emergency Off

X

X

D*, L, S

Ambient Overtemperature

X, R

R

D, S

Blower Failed

X

D, S

Equipment Overtemperature

X

D, S

Overtemperature Timeout

X

D, F

Load On UPS

R

New Alarm

R

R

Module Summary Alarm

R

X

S

System Summary Alarm

R

Battery Exercise

X

Battery Overtemp

X

D, S

D = Auto-Dial initiated
D* = Auto-Dial initiated through Auto Transfer to

Bypass if load is on UPS

D# = Auto-Dial initiated through Module N (1-6)

off-line

E = message displayed on Status Report screens

F = freezes the History Status Report memory buffer
L = latches the displayed alarm message
R = Remote Alarm Contact (optional on MMU)
S = Summary Alarm (System or Module) initiated
X = message displayed on Monitor/Mimic screen

and audible alarm