14 alarm and status messages, Module status messages, Figure 51 scc status and alarm message areas – Liebert 1000kVA User Manual

Page 69: System status messages

Advertising
background image

Operation

63

3.2.14 Alarm and Status Messages

Module Status Messages

The module status messages indicate how many UPS modules are included in the system and the

present status of each module.
The following status messages may appear in the module status area.
1. MOD N: A module status message line is displayed for each UPS module in the system. Up to six

(6) modules may be included in a multi-module system. The N in the message will indicate a

specific UPS module number, 1 through 6.

2. ON LINE: The UPS module output circuit breaker is closed and power from the module is available

to the SCC. The module output is sharing the critical load if the UPS Output Breaker is closed.

3. OFF-LINE: The UPS module output circuit breaker is open. More specific alarm messages are

displayed at the UPS module.

4. SUM ALM: The Module Summary Alarm has been activated by one of the alarm messages listed

in two tables

SCC and module remote monitor indications and Other alarms that

activate summary alarms

in 3.2.6 - System Configuration Screens. The specific alarm

message is displayed at the UPS module.

5. COM FAIL: The UPS module is not communicating with the SCC. This could mean loss of power

to the UPS module controls, a disconnected cable or a control logic failure (detected by watchdog

timer. Call Liebert Global Services if you require assistance. To resume communication after

control power is restored, sequence display to Master Menu.

Figure 51 SCC status and alarm message areas

System Status Messages

The system status messages indicate whether the static bypass switch is connected or disconnected,

through the manually operated Static Switch Disconnects (see Figure 9). The status messages

also advise the operator when a transfer or retransfer between the UPS system and bypass line is per-

mitted, based on matching voltage, frequency and phase.
The following status messages may appear in the system status area.
1. Static Switch Connected: The static switch is connected (the disconnect switches are closed—

ON) and is ready to provide a current path from the bypass input to the load.

2. Static Switch Disconnected: The static switch is disconnected (the disconnect switches are

open—OFF) for maintenance procedures.

3. OK to Transfer: The UPS system voltage, frequency and phase match the bypass line. This

means that a transfer between the bypass line and the UPS system is permitted.

4. Not OK to Transfer: Either the UPS or bypass voltage, frequency or phase is not within the

specified limits or the static bypass switch is not available. Therefore, manually initiated transfer

between the bypass line and the UPS system is not permitted. Emergency or overload transfer to

bypass may still be available provided the “Static Switch Unable” alarm is not indicating.

UPS RATINGS

LOAD

Byp Not Avail
Static Sw Unable
Module Sum Alm

UPS INPUT PWR

BYPASS INPUT

A-B

B-C

C-A

0V

0V

0V

0 Hz

0V

0V

0V

A-B

B-C

C-A

Not OK to Transfer
Static Switch Connected

MOD 1 ON LINE SUM ALM
MOD 2 ON LINE SUM ALM
MOD 3 ON LINE SUM ALM

A-B

B-C

C-A

480V

480V

480V

60.0 Hz

SCCT 1600

OUTPUT VOLTAGE

627 KVA / 502 KW

755A

755A

755A

3 OF 3 MODULES

CONNECTED
REDUNDANT

A

B

C

Time To Overload
Transfer: XXXX SEC

LOAD BLOCK

MESSAGES

ALARM

MESSAGES

MODULE STATUS

MESSAGES

SYSTEM STATUS

MESSAGES

© 1989-2003

Advertising