Liebert 1000kVA User Manual

Page 73

Advertising
background image

Operation

67

UPS SYSTEM (Cont’d.)

Overload

Transfer

SCC

D, F, L, S

The load on the UPS has exceeded the current versus time window of

system overload capacity. The UPS system transfers the load to bypass.

Reduce the load. If the system does not initiate an automatic load

retransfer, manually retransfer the critical load from the bypass line to the

UPS. Reset the alarm.

Module Summary

Alarm

SCC

S

An alarm message (see lists in SCC and module remote monitor

indications and Other alarms that activate summary alarms in 3.2.6 -

System Configuration Screens) or the watchdog timer has activated the

Module Summary Alarm.

Clear alarm conditions, if possible.

MMU

R

Module N Off

Line

SCC

D

The output circuit breaker of Module N is open. The number N will identify

the module (1 through 6).

Review active alarms at Module N and clear alarm conditions, if possible.

MMU

R

Inverter

Nonsynchronized

MMU

Inverter output is not synchronized with the UPS system critical bus. This

also means the output circuit breaker is open and should not be closed

until the output is in sync. This condition may correct itself. If not, shut

down the UPS module and then perform a start-up procedure.

Contact Liebert Global Services if condition persists.

Overload

Shutdown

MMU

D, F, L, S

The UPS output current has exceeded 175% of the rated full load or the

overload capacity has been exceeded. The UPS module is taken off-line

and shut down.

Contact Liebert Global Services at once. Do not attempt to reset circuit

breakers.

Reverse Power

MMU

D, F, L, S

Excessive reverse power flow from the critical bus into the UPS inverter

has occurred, probably because of low inverter output voltage or a phase

mismatch. The UPS module is taken off-line and is shut down.

Contact Liebert Global Services immediately. Do not attempt to reset

circuit breakers.

Rectifier Fuse

Blown

MMU

D, F, S

At least one of the fuses has opened or a rectifier fault was detected. UPS

module is taken off-line and is shut down.

Contact Liebert Global Services immediately. Do not attempt to reset

circuit breakers.

Inverter Fault

MMU

D, F, S

At least one of the fuses has opened or an inverter fault was detected.

The UPS module is taken off-line and is shut down.

Contact Liebert Global Services immediately. Do not attempt to reset the

circuit breakers.

Communication

Failure

SCC

S

The COM FAIL status message is as important as an alarm message.

Refer to 3.2.14 - Alarm and Status Messages.

Battery Cycle

Buffer Warning

MMU

D, S

The optional Battery Cycle Monitor can retain information about the last

132 battery discharge events. When the storage buffer approaches its

capacity, this warning message is broadcast via terminal and modem

communication channels and a complete listing of all records is sent to

the terminal port. The message clears after 30 seconds.

Battery Exercise

MMU

Battery self-test can be enabled from System Options screen. For test to

start, the following conditions must be valid:

1. No Battery Overtemp Alarm must exist.

2. Battery input and output circuit breakers must be closed.

3. All three input volt phases must be within nominal range (+10%, -20%).

4. DC volts must be greater than (DC Ref) -20V. For a 540 bus, the

nominal float voltage for 240 cells (the DC voltage reference setting) the

DC voltage on the battery must be greater than 520VDC.

5. Battery charge must be greater than 90%.

6. Load must be greater than 15%.

Table 9

Alarm messages - meaning and corrective action (continued)

Alarm

Message

Cabinet

Location

Special

Functions

Meaning and Corrective Action

Table 9 Abbreviations
D = auto-dial;

L = latches

E = logs only;

R = remote

F = freezes;

S = summary

D* = auto-dial initiated by Auto Transfer to Bypass if load is on UPS when alarm occurs
D# = auto-dial initiated through Module N (1-6) off-line

Advertising