3.3.4 Input Power Failure—Load on Battery

If the utility AC power source fails or is outside the acceptable range, the battery plant becomes the

power source for the UPS module inverters. The UPS system continues to supply power to the critical

load and also to the controls of the UPS modules and the SCC.
You can use the Battery Time screen at the UPS modules to monitor the present battery voltage com-

pared to the shutdown value. The length of time the battery can sustain the load depends on the size

of the load and the size and condition of the battery plant. The battery plant is usually large enough

to supply a 100% rated load for 15 minutes.
Alarm messages that indicate battery status are Battery Discharge, Low Battery and Battery Shut-

down. The voltage limits for these alarms are displayed on the UPS module Alarm Limit Settings

screen. These limits were selected for your installation by Liebert Global Services during initial start-

up.
The battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge and the

current in Amperes. Maximum battery discharge current ranges from 326 amps (for 150kVA) to 1620

amps (for 750kVA). Refer to the separate Installation Manual or drawings for specific data on your

system.

Figure 56 Input power fail—load on battery

BIB

SKRU

MIB

MBB

#2

UPS

CB1

#1

UPS

CB1

System

Controls

#3

UPS

CB1

RIB

RIB

RIB

BFB

Output

SBB

SBS

I

CB2

I

I

CB2

CB2

R

R

R

SCCT

SCCT

(can accommodate up to 6 UPS modules)

To Critical Load

Battery

MBD

Battery

MBD

Battery

MBD

Advertising