Figure 9, Table 2 – Liebert 1000kVA User Manual

Page 28

Advertising
background image

Operation

22

Figure 9

Operator controls, typical SCCT System Control Cabinet

Table 2

Typical SCCT System Control Cabinet operator controls

Item

Description

Function

1

UPS Output Circuit

Breaker

This motorized circuit breaker connects the critical load to the UPS system

output.

2

System Bypass Circuit

Breaker

This motorized circuit breaker connects the critical load to the bypass line.

3

Operator Control Panel

Refer to Figure 10 for controls available on this panel.

4

Interlock Button

(on rear of Control Panel)

Refer to Figure 11.

5

Close Bypass Switch

(behind door)

Refer to Figure 11.

6

Bypass Reset Switch

(behind door)

Refer to Figure 11.

7

Static Switch Disconnects

(behind door)

These manually operated switches disconnect the static switch from the

bypass line and from the critical load. They are normally ON (closed). Turn

them OFF (open) only to isolate (disconnect) the static switch for

maintenance procedures. For SCCT less than 1600A, the static switch

disconnects are contactors that open automatically upon loss of bypass input

power and close automatically when bypass power is restored. Control power

fuse disconnects are used to manually open the contactors for maintenance.

8

Reset Switches (SW1) for

Static Switch Disconnects

(behind door)

Press these two switches before closing Static Switch Disconnects when

recovering from a shutdown that includes loss of Control Power. Green LED

on means Control Power is available. Red LED on means Reset Switch

needs to be pushed. Only SCCI and SCCC control cabinets and SCCT

1600A and larger.

9

Control Power Disconnect

(behind door)

Normally ON. Fuseblocks that are labeled F7 through F10. Turn OFF Control

Power only when required for maintenance procedures.