Table 5 – Liebert 1000kVA User Manual

Page 47

Advertising
background image

Operation

41

Table 5 shows the alarm conditions that stop the History Status buffer from gathering data.

The History Status buffer does not resume collecting new frames until the fault is cleared and the

Alarm Reset pad is pressed for more than 5 seconds (or until the screen clears).

Table 5

Alarm conditions that freeze history data gathering

Alarm in SCC

Alarm in Module

Auto Transfer to Bypass

DC Cap Fuse Blown

Output Overvoltage

DC Overvoltage Shutdown

Output undervoltage

Inverter Fault

Overload Transfer

Low Battery Shutdown
Overload Shutdown
Overtemperature Timeout
Rectifier Fuse Blown
Reverse Power

NOTE
The Emergency Off alarm will also freeze the SCC History Status buffer with the Auto

Transfer to Bypass alarm (if the load is on the UPS system when the alarm condition occurs).