7 emergency modules off, Figure 59 emergency modules off, Emergency modules off – Liebert 1000kVA User Manual

Page 86: Operation 80, Scct

Advertising
background image

Operation

80

3.3.7 Emergency Modules Off

The Local Emergency Modules Off (LEMO) mode is used to remove power from all UPS system com-

ponents and the critical load will continue to be supplied through the bypass line.
The Emergency Module Off control is a guarded pad on the SCC Control Panel (see Figure 10).
Lift the cover and press the pad. The load will be transferred to bypass and the battery (MBD), input

and output circuit breakers will be opened (tripped). This will remove power from all UPS system

components except the controls, system bypass circuit breaker and the static switch.
Refer to 3.4.5 - Shutdown Procedures.