13 battery equalize screen, Figure 50 battery equalize screen, Caution – Liebert 1000kVA User Manual

Page 68

Advertising
background image

Operation

62

3.2.13 Battery Equalize Screen

Go to the Master Menu and move the highlighted cursor to BATTERY EQUALIZE. Press the Select

pad and the Battery Equalize screen is displayed.
The Battery Equalize screen enables the operator to adjust the battery equalize time. It is also used to

choose between auto and manual battery equalize recharging modes. Note that AUTO MODE can be

selected only from the System Control Cabinet (SCC). Selections made at the SCC override previous

selections made at the UPS modules.
When the input utility power is interrupted, the battery supplies DC power to the UPS module invert-

ers so there is no interruption of power to the critical load. When the AC input power is restored, the

battery equalize recharging circuit can be activated automatically or manually to increase the module

rectifier/charger output voltage to recharge the battery. The battery equalize circuit may also be man-

ually activated at any time during normal float (constant) voltage operation. The equalizing time can

be adjusted from 0 to 72 hours.

Figure 50 Battery equalize screen

EQUALIZE TIME PERIOD. This selection permits the operator to adjust the battery equalize time

in one hour increments from 0 to 72. The battery equalize time must be greater than zero for the bat-

tery to begin recharging in both the AUTO and the MANUAL modes. This period is set by use of the

Up/Down pads and Select pad.
When the battery is at full voltage (not being recharged), this selection reads EQUALIZE TIME

PERIOD (hrs). When the battery is recharging, this selection reads EQUALIZE TIME REMAIN-

ING (hrs). After the equalize recharge time has expired, the indication returns to the preset equalize

time.
STOP EQUALIZE CHARGE. This selection lets the operator halt the equalizing charge to the bat-

tery at any time, whether the circuit was activated automatically or manually.
MANUAL MODE. This mode enables the operator to manually initiate a battery equalize charge to

raise the DC bus voltage to correct a non-uniformity in the individual cell voltages or specific gravity

readings.
AUTO MODE (SCC only). When the battery recharge control logic is in the AUTO MODE, the UPS

module battery chargers attempt the equalization process only if the EQUALIZE TIME PERIOD is

greater than zero, the battery voltage has been at or below the Battery Discharging alarm limit for

longer than 30 seconds and the battery breakers (MBD) are closed.

!

CAUTION

Do not use the Battery Equalize mode if you have valve-regulated, sealed-cell

(maintenance-free) batteries. Refer to your battery manufacturer’s manual,

available on the manufacturer’s Web site.

EXIT

SECURITY ACCESS

BATTERY EQUALIZE RECHARGING

0
NO
NO
YES
NO

EQUALIZE TIME PERIOD (hrs.) ...........
STOP EQUALIZE CHARGE ...................
MANUAL MODE .....................................
AUTO MODE ..........................................
MANUAL / RESET TO AUTO MODE ......

CURSOR UP

CURSOR DOWN

CHOOSE

UP :

DOWN :

SELECT :

© 1989-2003

Advertising