Operation

40

History Status

The History Status screen displays 64 frames, of 4 milliseconds each, from the Present Status screen.

Note that the values for output volts and amps are updated once each millisecond. Alarms are listed

in the sequence they occurred, within 1 millisecond resolution. The frames are stored in a buffer (a

computer information storage technique). The buffer stores the frames in a first in, first out sequence.

As a new frame enters the buffer the oldest one is released.
When a designated fault occurs (see list below), the buffer stores information for the next 24 frames

and then freezes (stops gathering information). At that time, the History Status screen contains

40 frames before the fault, the frame when the fault occurred and 23 frames after the fault. This

64-page report is a very useful diagnostic tool for the operator or Liebert Global Services. Use the Up

and Down pads to view the screens.

Figure 25 History status report screens

OUTPUT VOLTS
OUTPUT AMPS
OUTPUT FREQUENCY
LOAD KVA
BYPASS VOLTS

A

480
420

480

DC

B

480
420

480

TIME

LOAD

349

C

480
420

480

HERTZ

60.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP :

DOWN :

SELECT :

HISTORY STATUS

MODULE-0

04/10/97

16:49:21

FRAME 36

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Output Ov-volts

OUTPUT VOLTS
OUTPUT AMPS
OUTPUT FREQUENCY
LOAD KVA
BYPASS VOLTS

A

380
530

380

DC

B

380
530

380

TIME

LOAD

349

C

380
530

380

HERTZ

50.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP :

DOWN :

SELECT :

HISTORY STATUS

MODULE-0

04/10/97

16:49:21

FRAME 36

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Output Ov-volts

OUTPUT VOLTS
OUTPUT AMPS
OUTPUT FREQUENCY
OUTPUT VOLTS
OUTPUT AMPS
BATTERY VOLTS
OUTPUT VOLTS
OUPUT AMPS
BATTERY AMPS
INPUT VOLTS
INPUT AMPS
OUPUT VOLTS
OUTPUT AMPS
LOAD KVA

A

480
325

480
325

480
325

0
0

480
325

DC

390

-645

B

480
325

480
325

480
325

0
0

480
325

TIME

0:01

LOAD

270

C

480
325

480
325

480
325

0
0

480
325

HERTZ

60.0

NEXT FRAME

PREVIOUS FRAME

EXIT

UP :

DOWN :

SELECT :

HISTORY STATUS

MODULE-0

01/17/98

11:21:59

FRAME 100

ORDER - 000000

SITE ID - 00000

SITE TAG - 0000000

**** ACTIVE ALARMS **** Batt Discharging

Low Batt Warning

Advertising