Table 3, Series 610 ups and scc operator control panels, R to figure 10 – Liebert 1000kVA User Manual

Page 29

Advertising
background image

Operation

23

Figure 10 Series 610 UPS and SCC operator control panels

Table 3

Series 610 UPS and SCC operator control panels

Item Description (Location)

Function

1

Display Screen

(SCC and modules)

This screen displays all vital UPS information in one convenient location. All of the

UPS monitoring functions and conditions are indicated here.

2

Up

(SCC and modules)

This touch-sensitive pad (button) is used to move the cursor up through various

selections present on the display screen. Note that all pads on this control panel

have touch-sensitive switches behind them.

3

Down

(SCC and modules)

Similar to the Up pad, this pad is used to move the cursor down through the

various selections present on the display screen.

4

Select

(SCC and modules)

After choosing the desired item (with highlighted cursor) from the display screen

with the Up and Down pads, pushing this pad tells the microprocessor to go to the

highlighted selection.

5

Alarm Reset

(SCC and modules)

This pad is used to clear all of the alarm conditions that are no longer present.

However, all active alarms remain in memory and on the applicable screens until

they are corrected.

6

Voltage Adjust

(SCC only)

This push-to-turn knob permits adjustment of the UPS output voltage to meet load

requirements or to match the bypass voltage before transferring the load to or from

bypass.

7

UPS

(SCC only)

This pad activates the circuits that connect the UPS to the critical load (a

retransfer). When this pad is pushed (along with Control Enable), the UPS output

circuit breaker closes and the bypass circuit breaker opens.

8

Bypass

(SCC only)

This pad activates the circuits that connect the bypass line to the critical load (a

transfer). When this button is pushed (along with Control Enable), the bypass

circuit breaker closes and the UPS output circuit breaker opens.

9

Control Enable

(SCC and modules)

This pad must be pressed simultaneously with the UPS, Bypass, Battery Trip or

Output Trip pads to activate them.

10

Horn Off

(SCC only)

This pad is used to silence the alarm horn after it is activated. When this switch is

pressed, the alarm horn is silenced but the active and latched alarm messages

remain on the screen. The alarm messages still displayed stop flashing to indicate

they have been acknowledged.

11

Alarm Horn and

Red LED (SCC only)

This electronic horn sounds to alert nearby personnel whenever a new alarm

occurs. A red LED (light emitting diode) is located in the middle of the alarm horn.

12

Emergency Module

Off (SCC only)

During an emergency, pressing this guarded switch will transfer the load to bypass

and then shut down the UPS modules. The load will remain on bypass power.

(Refer to 3.4.5 - Shutdown Procedures.)

13

Battery Trip

(modules only)

This pad can be used (along with Control Enable) to trip the module battery

disconnect (MBD) circuit breaker open (disconnecting the battery from the UPS

module).

14

Output Trip

(modules only)

This pad can be used (along with Control Enable) to trip the module output circuit

breaker open (disconnecting the module from the UPS system).

Numbers are used

as keys to data in

Table 3, below.