Remote monitor, Table 6 scc and module remote monitor indications, Table 7 other alarms that activate summary alarms – Liebert 1000kVA User Manual

Page 57: Table 6, Scc and module remote monitor indications, Table 7, Other alarms that activate summary alarms

Advertising
background image

Operation

51

Figure 39 Monitor/Mimic display example: Continuous Duty Static Switch

Remote Monitor

The Remote Monitor Panel (optional) displays eight (8) alarms. These alarms are also available for

customer use through a set of contacts on a separate terminal board.
When the New Alarm, System Summary Alarm or Module Summary Alarm is activated, you can get

more information at the Operator Display Panel or through a remote terminal. Refer to 3.2.15 - Com-

munication Interfaces.

The following alarms, as well as those listed above, will activate the System Summary Alarm or the

Module Summary Alarm.

Table 6

SCC and module remote monitor indications

SCC Remote Monitor Indications

Channel

Module Remote Monitor Indications

Load On UPS

CH1

Output CB Open

Load On Bypass

CH2

Battery CB Open

Battery Discharging

CH3

Battery Discharging

Low Battery Warning

CH4

Low Battery Warning

Overload

CH5

Control Failure

Ambient Overtemp

CH6

Ambient Overtemp

System Summary Alarm

CH7

Module Summary Alarm

New Alarm

CH8

New Alarm

Table 7

Other alarms that activate summary alarms

System Summary Alarm

Activation

Module Summary Alarm

Activation

Control Power Fail

Blower Failed

Emergency Off

Control Power Fail

Module Summary Alarm

DC Capacitor Fuse Blown

Output Over/Under Frequency

DC Ground Fault

Output Overvoltage

DC Overvoltage Shutdown

Output undervoltage

Emergency Off

Overload Transfer

Equipment Overtemperature

Static Switch Unable

Inverter Fault
Low Battery Shutdown
Overload
Overload Shutdown
Rectifier Fuse Blown
Reverse Power

BYPASS INPUT

A-B

B-C

C-A

480V 480V 480V

60.0Hz

UPS INPUT PWR

A-B

B-C

C-A

480V 480V 480V

UPS RATINGS

SCCB 1600

OUTPUT VOLTAGE

A-B

B-C

C-A

480V 480V 480V

60.0Hz

LOAD

627 KVA / 502 KW

A

B

C

755V 755V 755V

3 OF 3 MODULES

CONNECTED
REDUNDANT

MOD 1 ON LINE

MOD 2 ON LINE

MOD 3 ON LINE

CDSS

OK to Transfer

Static Switch Connected