Figure 11 Switches behind SCC control panel door

Table 4

Series 610 UPS and SCC operator control panels

Item

Description (Location)

Function

1

Interlock Button

(on rear of Control Panel)

Press this button to make authorized changes to any site parameter protected

by the Security Access function. These include the time, date, auto-dial phone

number and other site parameters.

2

Bypass Reset Switch

(SW1, on Transfer

Relay Board)

Press this button to reset the transfer relays during start-up, after an

Emergency Power Off shutdown. You must press this button before the Close

Bypass Switch (Item 3).

3

Close Bypass Switch

(SW1, on System

Interface Board)

Press this button to close the Bypass circuit breaker during a start-up

procedure, if it remains open after a shutdown procedure (refer to 3.4.1 - SCC

Start-Up Procedure). Note that the Static Switch Disconnects must be OFF to

reset the Bypass circuit breaker. See also Bypass Reset Switch (Item 2).

Numbers are used

as keys to data in

Table 4, below.