3.3.9 System Shutdown

Perform a System Shutdown procedure when you must disconnect the UPS system components from

all power sources when required for maintenance procedures.
Use the Shutdown Procedures screen when performing a manual System Shutdown.
Refer to 3.4.5 - Shutdown Procedures.
Refer to 3.3.10 - Maintenance Bypass.
Before performing any maintenance on your Liebert Series 610 UPS System, observe ALL of the

WARNINGS in 4.0 - Maintenance.

Figure 61 System shutdown

3.3.10 Maintenance Bypass

Maintenance Bypass switchgear (cabinet, panelboard, switchboard or custom switchgear) allows you

to totally isolate the UPS system from all power sources, while you maintain power to the critical

load.
Your installation may have a two-breaker, three-breaker or four-breaker maintenance bypass or none

at all. The main differences are the locations of the Rectifier Input Breaker and the Bypass Input

Breaker (BIB).
Another option that may be present at your site is an alternate power source (generator) and an auto-

matic transfer switch (ATS).
Note that to totally isolate the UPS system from all power sources, the Main Input switchgear and

battery circuit breakers must also be opened

!

WARNING

Lethal voltages are present within this system even when it is not on or when power is not

being supplied. Observe all cautions and warnings in this manual. Failure to do so could

result in serious injury or death. Do not work on or operate this equipment unless you are

fully qualified to do so! Never work alone.

BIB

SKRU

MIB

MBB

I

R

CB2

System

Controls

BFB

Output

SBB

SBS

BFB

I

R

I

R

CB2

CB2

#2

UPS

CB1

#1

UPS

CB1

#3

UPS

CB1

RIB

RIB

RIB

SCCT

SCCT

(can accommodate up to 6 UPS modules)

To Critical Load

Battery

MBD

Battery

MBD

Battery

MBD