3.2.3 Module Monitor/Mimic Display Screen

From module Master Menu move the highlighted cursor to MONITOR/MIMIC DISPLAY. Press the

Select pad and the Monitor/Mimic screen is displayed.
The Monitor/Mimic display screen is a simplified block diagram of the UPS module and power connec-

tions. This screen gives the operator an overall view of the power flow through the UPS module. The

screen consists of three major sections: the input/UPS metering section, the load metering section and

the status and alarm message areas. The metered parameter values on the Monitor/Mimic screen are

updated at one second intervals.

Figure 15 Module Monitor/Mimic display screen

Input Metering Displays

Item 1 - UPS Input Pwr: This block displays the UPS module input voltage and current. The Mod-

ule Input breaker is shown to the right of this block. The status of the circuit breaker is illustrated as

open or closed.
Item 2 - Battery: The battery block displays the DC bus voltage and the charge or discharge current

to or from the battery. This block reads MODULE DC BUS when the battery circuit breaker is open

and BATTERY when the battery circuit breaker is closed during normal operation. This block reads

BATTERY EQUALIZE when the battery equalize charge voltage is used to recharge the battery.

This block also shows BATTERY TEMPERATURE when the battery temperature sensor option is

installed. The Module Battery Disconnect (MBD) is shown to the right of this block. The status of the

circuit breaker is illustrated as open or closed.

Output Metering Displays

Item 3 - UPS Ratings: The module part number and kVA rating are specified at the top of this block.

The UPS output voltage and frequency are also displayed in this block. The Module Output breaker is

shown to the right of this block. The status of the circuit breaker is illustrated as open or closed.
Item 4 - Load: This block displays the module output power to the critical load in kVA and kW. The

critical load current per phase is also displayed in this block.

NOTE
All voltage readings are phase-to-phase measurements (A-B, B-C and C-A). All current

readings are phase measurements (A, B and C).

UPS INPUT PWR

BATTERY

VOLTS 540
AMPS 15 CHARG

UPS RATINGS

A-B

B-C

C-A

OUTPUT VOLTAGE

LOAD

A

B

C

270 KVA / 217 KW

A-B

B-C

C-A

2

4

3

5

1

480V

480V

480V

350A 350A

350A

AP648-84

RATED 400 KVA

480V

480V

480V

60.0 Hz

325A

325A

325A

© 1989-2003

Advertising