8 remote emergency power off, Figure 60 emergency power off, Remote emergency power off – Liebert 1000kVA User Manual

Page 87: Operation 81, Scct

Advertising
background image

Operation

81

3.3.8 Remote Emergency Power Off

The Remote Emergency Power Off (REPO) mode is used to remove all power from the critical load.
The Remote Emergency Power Off control is a switch located remotely from the UPS system. It will

normally be in the same room as the critical load equipment. This mode can also be initiated by an

automatic contact closure in the same external circuit as the manually operated switch.
When you operate the Remote Emergency Power Off switch, all UPS circuit breakers are opened,

including the bypass circuit breaker. All power through the UPS is removed from the load. Typically,

the REPO circuit also opens the circuit breakers that provide power to the bypass lines and the UPS

controls.
Refer to 3.4.5 - Shutdown Procedures.

Figure 60 Emergency power off

BIB

SKRU

MIB

MBB

I

R

#2

UPS

CB1

CB2

System

Controls

RIB

RIB

RIB

BFB

SBB

SBS

RIB

RIB

RIB

BFB

#1

UPS

#3

UPS

I

R

#1

UPS

CB1

I

R

#3

UPS

CB1

CB2

CB2

Output

SCCT

SCCT

(can accommodate up to 6 UPS modules)

To Critical Load

Battery

MBD

Battery

MBD

Battery

MBD