5 one module off-line, Figure 57 one module off-line, load on ups, One module off-line – Liebert 1000kVA User Manual

Page 84: Scct, Operation 78

Advertising
background image

Operation

78

3.3.5 One Module Off-Line

A multi-module UPS system can be supplied with a back-up (redundant) UPS module, which is the

typical configuration. A redundant system includes one more module than the number required to

supply the critical load. A redundant system operates in the redundant mode if all modules are ON

LINE. Note that the UPS system can also operate in the redundant mode with one module OFF

LINE if the critical load is reduced so that not all ON LINE modules are required. The UPS modules

share the load and the critical load will remain on the UPS system if any one of the modules is discon-

nected (goes OFF LINE) for maintenance or because of an internal fault.
The system control logic monitors the connected critical load and the number of UPS modules ON

LINE. If the UPS system is operating in the redundant mode, the REDUNDANT status message

will be displayed at the System Control Cabinet (SCC). If the UPS system is operating in the non-

redundant mode (redundant module is OFF LINE or was not included in the system configuration),

the NON-REDUNDANT status message is displayed at the SCC. In the Non-Redundant mode, the

critical load will be transferred to bypass if any UPS module goes OFF LINE and you must transfer

the load to bypass in order to perform maintenance on any UPS module.

Figure 57 One module off-line, load on UPS

BIB

SKRU

MIB

MBB

I

R

#2

UPS

CB1

CB2

System

Controls

RIB

RIB

RIB

BFB

Output

SBB

SBS

RIB

RIB

RIB

BFB

I

R

#1

UPS

CB1

CB2

I

R

#3

UPS

CB1

CB2

SCCT

SCCT

(can accommodate up to 6 UPS modules)

To Critical Load

Battery

MBD

Battery

MBD

Battery

MBD

Advertising