3.3.6 Off Battery

The battery plant can be disconnected from the UPS modules, if required for battery maintenance, by

opening the module battery disconnect (MBD) circuit breaker(s). In this situation the UPS system

will continue to supply conditioned power to the critical load, but if input power fails the UPS system

cannot supply power to the load.

Figure 58 Load on UPS—battery not available

!

CAUTION

When the UPS system is operating with the module battery disconnect (MBD) circuit

breaker(s) open, the critical load is not protected from loss of the utility source power.
For battery maintenance on multi-module systems, Liebert recommends taking the

module requiring maintenance off-line before beginning the work. This precaution will

minimize disturbances on the system bus if input power fails during the maintenance

work.

BIB

SKRU

MIB

MBB

I

R

#2

UPS

CB1

CB2

I

R

#1

UPS

CB1

System

Controls

I

R

#3

UPS

CB1

CB2

RIB

RIB

CB2

RIB

BFB

Output

SBB

SBS

SCCT

SCCT

(can accommodate up to 6 UPS modules)

To Critical Load

Battery

MBD

Battery

MBD

Battery

MBD