15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit

0

0

0

Word
n+3

15 14 13 12 11 10

9

8

Bit

PT status control bits

0

0

PT status control designation

 

     

Section 5-4

6-4

NT600S Status Control

The statuses of the NT600S can be controlled from the PC by writing control data
to the “PT status control bits” of the PT status control area allocated in the PC
memory.

Buzzer sounds

Screen off

PT status control area

Screen switch setting

Control data

NT600S

PC

PT status control bits

Copy memory table
setting

6-4-1

Controllable NT600S Functions

[“PT status control bits” of the PT status control area]

Item Controlled

1 (ON)

0 (OFF)

Screen display (Note 1)

ON

OFF

Processing priority
registration
(Note 2)

ON

OFF

Continuous buzzer

ON

OFF

Intermittent buzzer

ON

OFF

Backlight mode
(Note 3)

ON

Flash

Note 1: When “Screen display = ON”, the back-

light/EL display is ON and when
“Screen display = OFF”, the backlight/
EL display is OFF.

Note 2: Priority registration is only valid when

NT link (1:N) is set.

Note 3: These functions cannot be used for

NT600S-ST211.

The PC status control bits remain unchanged if the NT600S status is changed with
the screen attributes or memory switches, which means that the statuses of the
PT status control bits do not match the actual status of the NT600S. For example,
the buzzer may sound even though the setting for continuous buzzer bit 13 is
“OFF”.

In this kind of case, control the NT600S by using the PT status control bits.