Appendix e – Omron NT-series Programmable Terminal V022-E3-1 User Manual

Page 282

Advertising
background image

1

6

9

5



.   .(          $0&

Appendix E



Wiring Connections

The NT600S does not use pin 4 (RS) or pin 5 (CS). Either short the RS and CS pins of the PC connector together
or set the CTS setting selector switch at the rear face of the host link unit to “0V” (see



in the figure).

Connect the cable shielding wire to the connector cover and pin 1 at the host link unit end of the cable only.

1

2

3

4

5

6

7

8

9

Pin
number

Abbrevi-
atioon

FG

SD

RD

RS

CS

--

--

SG

RS-232C
interface

RS-232C
interface

Pin
number

Abbrevi-
atioon

1

2

3

4

5

6

7

8

--

FG

SD

RD

RS

CS

--

SG

--

--

Shielding
wire

25-pin connector

NT600S

PC (host link unit)

--

--

--

ER

--

--

--

20

+5V



Connecting an NT600S to a C-Series CPU (C



H)



C-Series CPU Unit (C



H) 9-pin Connector Specifications



Applicable CPU:

C20H/C28H/C40H/C60H



Electrical characteristics:

Complies with EIA RS-232C



Signal direction:

Signal input and output is relative to the PC.

Connector

Signal Name

Abbreviation

Signal Direction

Connector

Pin No.

Signal Name

Abbreviation

Input

Output

1

Frame ground

FG

--

--

2

Send data

SD (TXD)



3

Receive data

RD (RXD)



4

Request to send

RS (RTS)



5

Clear to send

CS (CTS)



7

Signal ground

SG (GND)

--

--

Advertising