Transportation and storage of the pt – Omron NT-series Programmable Terminal V022-E3-1 User Manual

Page 278

Advertising
background image

Note

 

 %   69 

Appendix D



Take the following points into account in order to prevent noise

(1) Avoid installing the unit in panels in which high-voltage equipment is also installed.

(2) Install the unit at a distance of at least 200 mm from power lines.

Power line

200 mm min.

200 mm min.

NT600S

(3) If the unit is installed next to equipment that generates a strong electric or magnetic field (solenoids, etc.), pro-

vide a gap of at least 40 mm.

40 mm min.

Solenoid

PT

When using the RS-232C +5V output, check the current capacity of the con-
nected equipment. The maximum current value of the NT20S +5 V output is 150
mA.

Transportation and Storage of the PT

Note on transportation

Pack the PT in the packaging intended for it before transporting it.

Note on storage

Maintain the storage ambient temperature (--20 to 70



C) and storage ambient humidity (35 to 85% RH).