Reference

 

     

Section 5-4

6-4-2

How to Control NT600S Functions

This section describes how to control the functions of the NT600S.



Restrictions on allocating words

The PT status control area (PC

PT) can be allocated to the PC memory areas

listed in the following table.

Symbol

C Series PCs

Allocated

CVM1/CV Series PCs

Allocated

DM

Data memory

Data memory

CH

Internal/Special Relay

Internal/Special Relay

TIM

Timer



Timer



CNT

Counter



Counter



HR

Holding Relay

--

AR

Auxiliary Relay

Auxiliary Relay



LR

Link Relay

--

: OK



: NG

Since all the CVM1/CV-series special auxiliary relays are allocated to the system,
they cannot be used for applications not related to the system.

The range of each memory area differs according to the PC type. See “Appendix L
PC Memory Map” (page 291) for more details.

Procedure

1. Use the support tool to allocate the PT status control area (PC

PT) to the PC

memory.

2. Create a PC program to write control data to the “PT status control bits” of the

PT status control area.



Control timing of PT status control bits

The PT status control area (PC

PT) is not read when the NT600S starts up. It

is only read, and control is only executed, when the contents of the PT status
control area are changed after the NT600S has been started up.

Since control of the NT600S statuses is executed after the bits corresponding to
the PT status control bits have changed, to execute control again the corre-
sponding bits must be specified again.

Application

This example is of the NT600S being used as a warning lamp by using PT status
control bits.



Support Tool Settings

Make the following setting using the support tool.

Allocated word for the PT status control area: 0100