Section 2-5

3-5-3

PC Switch Settings

When the NT600S and PC are connected to each other, set the conditions at the
PC CPU so as to enable the NT link communications.

The following is a general description of switch settings.



C-series C200HS, C200HX/HG/HE, CPM1, CQM1

Set the operating conditions to the PC system setting area when a C200HS or
CQM1 CPU is connected to the NT600S. The PC system setting area (data
memory) can be directly accessed from the peripheral tool (LSS etc.).

The following describes the switch settings so as to enable the PC system set-
tings. For the details of the operation with the PC system setting area, refer to the
“SYSMAC CQM1 Reference Manual” (W228-E1-



).

[Switch setting] (C200HS, C200HX/HG/HE, CQM1)



RS-232C port communication
condition settings
Set DIP switch 5 to OFF (right side)
to enable the PC system settings.

CPU unit DIP switch settings

[PC system setting area settings] (C200HX/HG/HE, CPM1, CQM1)

Write values to the PC system setting area (data memory) in accordance with the
CPU unit and port used for connection to the NT600S.

PC Side

Channel #

Writing Value

Settings

RS-232 port of
C200HX/HG/HE,
CQM1

DM6645

Port A of C200HX/
HG/HE

DM6555

4000

Use NT link (1:1)

Port B of C200HX/
HG/HE

DM6550

CPM1

DM6650