.   .(          $0&

Appendix E

Connecting an NT600S to an RS-232C/RS-422 Converter Unit (NT-AL001)

Connecting to an RS-232C/RS-422 converter unit allows transmissions over distances greater than 15 m (maxi-
mum of 500 m).

Max. 2 m

Max. 500 m

NT-AL001

Host

NT600S

RS-422A

RS-232C

When connecting a C200HX/HG/HE and an RS-232C/RS-422 converter unit, use
a converter unit whose lot number is 15Y5 or later. Converter units of lot numbers
previous to 15Y5 cannot be connected.



NT-AL001 RS-232C Connector Specifications (9-pin Type)

Electrical characteristics: Conform to EIA RS-232C

Signal direction: Signal input and output is relative to the NT-AL001.

Connector

Signal Name

Abbreviation

Signal Direction

Connector

Pin No.

Signal Name

Abbreviation

Input

Output

Connector cover

Grounding or earth for safety
purposes

FG

--

--

2

Send data

SD (TxD)



3

Receive data

RD (RxD)



4

Request to send

RS (RTS)



5

Clear to send

CS (CTS)



6

+5V input

+5V



9

Signal ground

SG (GND)

--

--