6-3 pc switch settings – Omron NT-series Programmable Terminal V022-E3-1 User Manual

Page 69

Advertising
background image



    $    ' ( )*+,

Section 2-6

3-6-3

PC Switch Settings

When the PC and NT600S units have been connected, set the switches at the
CPU module at the PC side in order to enable communication using the NT link
method.



C series, C200HX/HG/HE

Write the communication conditions directly to the “PC system area” (data
memory) using a peripheral tool (e.g., SYSMAC support software). For details on
the operation for setting the “PC system area”, refer to the “SYSMAC C200HX/
HG/HE Installation Guide” (W302-E1-



).

[PC system setting area setting]

With C200HX/HG/HE, the setting area differs according to the standard port of the
CPU module used for the connection or the port of the expansion communication
board.

Port

Channel #

Writing Value

Settings

C200HX/HG/HE
RS-232C port

DM6645

Use NT link (1:N)



= highest unit No

C200HX/HG/HE
port A

DM6555

5



00



= highest unit No.

in the maximum
number of connect-

C200HX/HG/HE
port B

DM6550

number of connect
able PTs (1 to 7). (*)

(*) When using C200HE, the PT unit No. range is 1 to 3.