Section 2-4



CVM1/CV series backplate mounted type: CV500-LK201

[Setting the front switches]

Set the operating conditions with the PC System Setting functions when a
CVM1/CV series host link unit is connected to the NT600S. The PC system set-
tings can be made directly from the peripheral tool (LSS etc.) or the PC system
setting information created with a peripheral tool can be transferred to the CPU.

The following describes the switch settings so as to enable the PC system set-
tings. For the details of the PC system settings, refer to the “SYSMAC CVM1/CV
Series Support Software Operation Manual (Details)” (W196-E1-



).



PC system setting (DIP SW1)
Set SW1 to “OFF”.
Communication is performed in accordance with the
values set in the PC CPU special I/O unit system
settings. The initial values in the system settings
are as follows:



Unit # (SW3 and SW4)
Set these switches to “0”.



I/O port selection (selector switch)
Set this to “RS-232C”.



CTS selection (DIP SW2 and SW3)
Set SW2 or SW3 to “ON”. (Set this always to “0V”.)
To use communication port 1, set SW2. To use commu-
nication port 2, set SW3.

Communications
port 1

Communications
port 2

I/O port
selector
switch

RS-232C

RS-422A

(RS-232C/

RS-422A)

(RS-232C)

Baud rate

: 9600 bps

Parity

: Even

Xon/Xoff control : Not performed
Communication mode

: Full duplex

Stop bit

: 2 bits

Data length

: 7 bits