Section 7-1

NT600S Symptoms

Cause

Remedy

Buzzer sounds, RUN LED
is OFF.

Malfunction due to external noise.

Distance the communication cable from the source of
the noise and insert a noise filter in the power supply
line.

Touch panel does not
respond

Malfunction due to external noise

Distance the communication cable from the source of
the noise and insert a noise filter in the power supply
line.

Touch panel is broken.

Check the touch panel by performing the touch panel
test in the I/O check in the maintenance mode.

PC mode changes to
monitor mode.

The NT600S changes the mode
during host link communication.

This is normal with the NT600S specification. When
using a PC that can also be connected using the NT
link, connect it with the NT link (the mode is not
changed when using the NT link).