2 how to install, 1 cabling, 1 cable lengths and number of codes – GE Industrial Solutions AF-600 FP Profibus DP User Manual

Page 10

Advertising
background image

2 How to Install

2.1 Cabling

2.1.1 Cable Lengths and Number of Codes

The maximum cable length allowable in one segment is dependent on the transmission speed. The total cable length includes drop cables if any. A drop cable is
the connection from the main network cable to each node if a T-connection is used instead of permissible cable length and maximum number of nodes/frequency
converters with 1, 2, 3 and 4 network segments.

Drop cable connection (i.e. T-connection) beyond the cable lengths indicated is not recommended, due to the increased risk of reflection occurring. Instead, GE
recommends direct connection of the frequency converter.

Note that a repeater is a node in both of the two segments it connects. The number of frequency converters is based on a single master system. If there are two
or more masters (e.g. PC tools), the number of frequency converters must be reduced correspondingly.

Maximum total network cable length:

Transmission speed

1 segment:

32 nodes

(31 drives)

[m]

2 segments:

64 nodes

(1 repeater, 61 drives)

[m]

3 segments:

96 nodes

(2 repeaters, 91 drives)

[m]

4 segments:

128 nodes

(3 repeaters, 121 drives)

[m]

9.6-187.5 kBaud

1000

2000

3000

4000

500 kBaud

400

800

1200

1600

1.5 Mbaud

200

400

600

800

3-12 MBaud

100

200

300

400

Total drop cable length limit per segment:

Transmission speed

Max. drop cable length per

segment

[m]

9.6-93.75 kBaud

96

187.5 kBaud

75

500 kBaud

30

1.5 Mbaud

10

3-12 MBaud

None

AF-650 GP/AF-600 FP Profibus DP Operating Instructions

9

2