PB-18 Node Address

Range:

Function:

126 N/A*

[0 - 126. N/A]

Enter the station address in this parameter or alternatively in the hardware switch. In order to adjust the
station address in par. PB-18 Node Address, the hardware switch must be set to 126 or 127 (i.e. all switches
set to ‘on’). Otherwise this parameter will display the actual setting of the switch.

PB-22 Telegram Selection

Option:

Function:

Select a standard Profibus telegram configuration for the frequency converter, as an alternative to using
the freely configurable telegrams in par. PB-15 PCD Write Configuration and par. PB-16 PCD Read Con-
figuration
.

[1]

Standard telegram 1

[101]

PPO 1

[102]

PPO 2

[103]

PPO 3

[104]

PPO 4

[105]

PPO 5

[106]

PPO 6

[107]

PPO 7

[108] *

PPO 8

[200]

Custom telegram 1

PB-23 Parameters for Signals

Array [1000]
Read only

Option:

Function:

This parameter contains a list of signals available for selection in par. PB-15 PCD Write Configuration and
par. PB-16 PCD Read Configuration.

PB-27 Parameter Edit

Option:

Function:

Parameters can be edited via Profibus, the standard RS485 interface, or the Keypad.

[0]

Disabled

Disables editing via Profibus.

[1] *

Enabled

Enables editing via Profibus.

PB-28 Process Control

Option:

Function:

Process control (setting of Control Word, speed reference, and process data) is possible via either Profibus
or standard fieldbus but not both simultaneously. Local control is always possible via the Keypad. Control
via process control is possible via either terminals or fieldbus depending on the settings in par.
O-50 Coasting Select to
par. O-56 Preset Reference Select.

[0]

Disable

Disables process control via Profibus, and enables process control via standard fieldbus or Profibus Master
class 2.

[1] *

Enable cyclic master

Enables process control via Profibus Master Class 1, and disables process control via standard fieldbus
or Profibus Master class 2.

PB-53 Profibus Warning Word

Range:

Function:

0 N/A*

[0 - 65535 N/A]

This parameter displays Profibus communication warnings. Please refer to the Profibus Operating In-
structions
for further information.

AF-650 GP/AF-600 FP Profibus DP Operating Instructions

59