6 warning and alarm messages, 7 fault messages via dp diagnostics – GE Industrial Solutions AF-600 FP Profibus DP User Manual

Page 81

Advertising
background image

AF-650 GP & AF-600 FP

Bit (Hex)

Comm. option STW (par. DR-84 Comm. Option STW)

00000001

parameters ok

00000002

configuration ok

00000004

clearmode active

00000008

baudrate search

00000010

waiting for parameterization

00000020

waiting for configuration

00000040

in data exchange

00000080

not used

00000100

not used

00000200

not used

00000400

not used

00000800

MCL2/1 connected

00001000

MCL2/2 connected

00002000

MCL2/3 connected

00004000

data transport active

00008000

not used

NB!
par. DR-84 Comm. Option STW is not part of extended diagnostics.

8.2.6 Warning and Alarm Messages

There is a clear distinction between alarms and warnings. When there is an alarm, the frequency converter will enter a fault condition. After the cause for the
alarm has been cleared, the master will have to acknowledge the alarm message before the frequency converter can start operating again. A warning, on the
other hand, may come when a warning condition appears, then disappear when conditions return to normal, without interfering with the process.

Warnings

Warnings within the frequency converter are represented by a single bit within a warning word. A warning word is always an active parameter. Bit status FALSE
[0] means no warning, while bit status TRUE [1] means warning. Any bit change in the warning word will be notified by a change of bit 7 in the status word.

Alarms

Following an alarm message the frequency converter will enter Fault condition. Only after the fault has been alleviated and the master has acknowledged the
alarm message by setting bit 7 in the control word, will the frequency converter resume operation. Alarms within the frequency converter are represented by a
single bit within an alarm word. An alarm word is always an action parameter. Bit status FALSE [0] means no fault, while bit status TRUE [1] means fault.

8.2.7 Fault Messages via DP Diagnostics

The standard DP function features an on-line diagnostics, which is active during DP initialization as well as data exchange mode.

AF-650 GP/AF-600 FP Profibus DP Operating Instructions