3.3 Configure the Frequency Converter

3.3.1 Drive Parameters

Pay particular attention to the following parameters when configuring the frequency converter with a PROFIBUS interface.

par. K-40 [Hand] Button on Keypad. If the Hand button on the frequency converter is activated, control of the drive via the PROFIBUS interface is disabled

After an initial power up the frequency converter will automatically detect whether a network option is installed in slot A, and set par. O-02 Control Word
Source
to [Op
tion A]. If an option is added or changed in or removed from an already commissioned drive, it will not change par. O-02 Control Word
Source
bu
t enter Trip Mode, and the drive will display an error

par. O-10 Control Word Profile. Choose between the GE Drive Profile and the PROFIdrive profile

par. O-50 Coasting Select to par. O-56 Preset Reference Select. Selection of how to gate PROFIBUS control commands with digital input command of the
control module.

NB!
When par. O-01 Control Site is set to [2] Control word only, then the settings in par. O-50 Coasting Select to par. O-56 Preset Reference Select will be overruled,
and all act on Bus-control.

par. O-03 Control Word Timeout Time to par. O-05 End-of-Timeout Function. The reaction in the event of a network time out is set via these parameters

par. PB-18 Node Address

par. O-07 Diagnosis Trigger

3.3.2 LEDs

The two bi-colour LEDs in the PROFIBUS module indicate the status of PRO-
FIBUS communication

The LED marked NS indicates the network status, i.e. the cyclical communi-
cation to the PROFIBUS master. When this light shows constant green, then
data exchange between the master and the frequency converter is active.

The LED marked MS indicates the module status, i.e. acyclical DP V1 commu-
nication from either a PROFIBUS master class 1 (PLC) or a master class 2
(DCT-10). When this light shows constant green, then DP V1 communication
from master classes 1 and 2 is active.

For details of the full range of communications status indicated by the LEDs,
please refer to the Troubleshooting chapter.